Zinsco Panel, Federal Pacific and Circuit Breaker Recalls: What Agencies and Courts Found

A dated record of every CPSC recall of US electrical panels, load centers and circuit breakers, set beside what the CPSC and a New Jersey court actually said about Federal Pacific Stab-Lok and what the record shows on Zinsco.
Older residential electrical panel with the cover off, showing rows of breakers and branch wiring
Data
CPSC Recalls Retrieval Web Service (full database, queried 2026-10-27); CPSC Release 83-008 (FPE, revised 2011); Superior Court of New Jersey, Yacout v. Federal Pacific Electric (2002)
Period
1983 to 2026
Release used
2026-10-22
Next release
Continuous: CPSC posts recalls as announced; ECW rechecks this register quarterly
Geography
United States (Canadian recalls labeled as cross-border)
Sources
30 (25 official)
The answer

No Zinsco panel appears in any CPSC recall. The CPSC recall database, queried October 27, 2026, lists 19 recalls of US panels, load centers, meter-main combinations and circuit breakers from 1988 to 2024, covering about 5.2 million units; none names Zinsco or Federal Pacific. CPSC closed its Federal Pacific Stab-Lok investigation in 1983 without a safety determination.

19CPSC recalls of panels, load centers, meter-main combinations and circuit breakers, 1988 to 2024[1]
5.2 millionUS units covered by those recalls where CPSC states a count (18 of 19 recalls)[1]
0CPSC recall records naming Zinsco, Sylvania-Zinsco, Federal Pacific or Stab-Lok, as of 2026-10-27[1]
2002Year a New Jersey court found Federal Pacific Electric distributed breakers not tested to UL standards as labeled[22]

CPSC has recalled 19 panel and breaker products since 1988

The federal recall record for panels and breakers is short and recent-weighted: 19 recalls in 36 years, most of them for overheating or failure to trip, and none for the brands most often discussed online.

ECW downloaded every record in the CPSC recall database on October 27, 2026 (10,058 recalls, the latest dated October 22, 2026) and reviewed every title, product name and description that mentions panels, load centers, breakers, AFCIs, GFCIs or meter combinations. Nineteen recalls cover residential or commercial panels, load centers, meter-main combinations and circuit breakers, including AFCI and GFCI breakers.

Thirteen of the 19 recalls describe overheating, fire risk or breakers that may not trip. Four describe GFCI or AFCI breakers whose protective function may not work. Two describe shock or arcing hazards from service equipment enclosures. Sixteen are residential-type equipment; three were large molded case breakers sold to commercial buyers.

CPSC recalls of panels, load centers, meter-main combinations and circuit breakers, US, 1988 to 2024 (newest first) Download CSV
DateBrandProductIssue (CPSC hazard, paraphrased)Action and evidence levelUS unitsRemedyRecall no.
2024-08-22SiemensSolarReady meter combos (meter, main breaker and panel)An interior connection can overheat (fire hazard)CPSC recall3,910Free on-site inspection and repair or replacement by a licensed contractor24346
2022-06-16Square D (Schneider Electric)QO Plug-On Neutral load centers made February 2020 to January 2022The load center can overheat (thermal burn and fire hazards)CPSC recall1,400,000Free inspection by trained electricians and free repair or replacement22159
2014-12-18Square D (Schneider Electric)PowerPact J-frame molded case circuit breakers, 150 to 250 ABreaker will not trip during an overload (fire, burn and shock risk)CPSC recall62,500Free replacement or repair kit plus labor credit (up to $300 or $150 per address)15050
2014-12-02EatonMBED 3042 series residential meter breakersElectrical components can be easily accessed (shock hazard)CPSC recall1,100Free remedy kit installed by a contractor15710
2014-03-18Square D (Schneider Electric)F and K frame molded case circuit breakersBreaker can fail to trip on overload (fire, burn and shock risk)CPSC recall28,400Free replacement plus up to $300 labor allowance per site14134
2010-09-23Siemens and MurrayCircuit breakers, load centers and meter combos, 15 to 50 AA spring clip can break, leading to excessive temperature, arcing or thermal damageCPSC recall2,200,000Free inspection by an electrician and free replacement10354
2010-08-02Counterfeit "Square D" (Miami Breaker)Counterfeit QO circuit breakersCounterfeit breakers can fail to trip when overloadedCPSC recall43,600Free inspection and replacement10749
2008-05-27Counterfeit "Square D" (Specialty Lamp International)Counterfeit QO and QOB circuit breakersCounterfeit breakers can fail to trip when overloadedCPSC recall371,000Free inspection, replacement or refund08286
2007-12-27Counterfeit "Square D" (North American Breaker Co.)Counterfeit QO circuit breakersCounterfeit breakers can fail to trip when overloadedCPSC recall50,000Free inspection, replacement or refund08151
2007-10-30Counterfeit "Square D" (Connecticut Electric)Counterfeit QO and QOB circuit breakersCounterfeit breakers could fail to tripCPSC recall64,000Free inspection, replacement or refund08054
2006-11-16Counterfeit "Square D" (Scott Electric)Counterfeit QO circuit breakersCounterfeit breakers might not trip when overloadedCPSC recall30,000Free inspection, replacement or refund07036
2004-11-19Midwest and GEMeter socket load centersLoose internal bolt connections could cause excessive heat or fireCPSC recall2,754Free repair or replacement05515
2004-11-03Square D (Schneider Electric)QO and Homeline AFCI circuit breakersAn electronic component failure can stop the AFCI detecting an arcCPSC recall700,000Free replacement through electrical contractors05035
2002-08-09Square DMA/MH molded case circuit breakersIncorrect lug screw torque could cause overheating and a fire hazardCPSC recall40,000Free repair02556
1999-04-22Square DCombination service entrance devices (meter and main breaker panel)Electrical arcing can occur when installed and energized (shock, electrocution, burn)CPSC recall12,200Free replacement99100a
1998-10-07Siemens and Murray2-pole GFCI circuit breakers used with hot tubs and spasBreakers could overheat and lose their ability to prevent injury or deathCPSC recall144,000Free replacement by qualified personnel99005
1988-11-12ChallengerType HAGF-15 and HAGF-20 single-pole GFCI circuit breakersA mechanical part may detach and stop the ground-fault feature from workingCPSC recall9,000Free replacement88095
1988-11-01Siemens (I-T-E)I-T-E load centers installed September 1986 to May 1987Components of an incorrect material could cause overheating and malfunctionCPSC recallNot statedFree inspection and correction88091
1988-04-13Square DSeries 1 two-pole GFCI circuit breakers, 15 to 30 AEarly failure of an electronic component may disable the shock protectionCPSC recall80,000Free replacement88022

Every entry is a CPSC recall. Issue text paraphrases the CPSC hazard statement. US units are the firm's approximate count as published by CPSC; 88095 counts breakers not yet located. Remedy wording shortened from the notice. Database queried 2026-10-27.

Source: [1][2][3][4][5][6][7][8][9][10][11][12][13][14][15][16][17][18][19][20] U.S. Consumer Product Safety Commission (SaferProducts.gov); U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission; U.S. Consumer Product Safety Commission

Two recalls hold most of the 5.2 million recalled units

US units covered by each CPSC panel or breaker recall, thousands

Two recalls hold most of the 5.2 million recalled unitsHorizontal bar chart: the 2010 Siemens and Murray recall covered about 2.2 million units and the 2022 Square D QO Plug-On Neutral recall about 1.4 million, followed by 700,000 Square D AFCI breakers in 2004 and 371,000 counterfeit breakers in 2008; the smallest recalls covered about 1,100 to 3,910 units.thousand unitsSiemens/Murray breakers, load centers (2012,200Square D QO PON load centers (2022)1,400Square D AFCI breakers (2004)700Counterfeit Sq D (Specialty Lamp) (2008)371Siemens/Murray spa GFCI breakers (1998)144Square D GFCI breakers (1988)80.0Counterfeit Sq D (Connecticut Electric) (264.0Square D PowerPact J-frame (2014)62.5Counterfeit Sq D (NABCO) (2007)50.0Counterfeit Sq D (Miami Breaker) (2010)43.6Square D MA/MH breakers (2002)40.0Counterfeit Sq D (Scott Electric) (2006)30.0Square D F and K frame (2014)28.4Square D service entrance devices (1999)12.2Challenger GFCI breakers (1988)9Siemens SolarReady meter combos (2024)3.9Midwest/GE meter load centers (2004)2.8Eaton meter breakers (2014)1.1

Source: U.S. Consumer Product Safety Commission recall notices; unit counts as published (approximate)

Recall size is concentrated. The 2010 Siemens and Murray recall (about 2.2 million units) and the 2022 Square D QO Plug-On Neutral recall (about 1.4 million) together hold 68.7% of the 5.2 million units. Twelve of the 18 recalls with a stated count covered 64,000 units or fewer each.

Federal Pacific Stab-Lok was never recalled: CPSC closed its probe in 1983 and a New Jersey court found consumer fraud in 2002

The official Federal Pacific record has three parts: a CPSC statement that closed an investigation without a safety determination, a federal appeals ruling about releasing the investigation files, and a New Jersey consumer fraud finding about UL testing and labels. None is a recall.

On March 3, 1983, CPSC announced it was closing its 2-year investigation into Federal Pacific Electric Stab-Lok residential breakers because "the data currently available to the Commission does not establish that the circuit breakers pose a serious risk of injury to consumers" (CPSC Release 83-008). The same release says the investigation began in June 1980 when Reliance Electric, FPE's parent, reported that many FPE breakers did not fully comply with UL requirements, and that "Commission testing confirmed that these breakers fail certain UL calibration test requirements."

The release cites the cost of further study against a $34 million budget for fiscal year 1983 and says staff had "insufficient data to accept or refute" Reliance's position that the breakers were safe in household use. On February 18, 2011, CPSC added a note telling electricians, homeowners, inspectors and real estate agents that the Commission "closed the matter without making a determination as to the safety of FPE circuit breakers" (CPSC).

On January 22, 1991, the U.S. Court of Appeals for the D.C. Circuit ruled on Reliance Electric's suit to block CPSC from releasing investigation records under the Freedom of Information Act. The court called the investigation "inconclusive" and noted the district court had cleared about 500 pages for release; it affirmed in part and vacated and remanded in part (Reliance Electric v. CPSC, 924 F.2d 274). The ruling concerns disclosure, not product safety.

In Yacout v. Federal Pacific Electric (Superior Court of New Jersey, Middlesex County, MID-L-2904-97), Judge Bryan D. Garruto wrote on August 15, 2002 that "Defendant FPE knowingly and purposefully distributed circuit breakers which were not tested to meet UL standards as indicated on their label," an unlawful practice under the New Jersey Consumer Fraud Act. The October 29, 2002 order granted partial summary judgment against FPE on that issue, and dismissed claims on sales before June 29, 1971 and claims by later home buyers (court papers, scanned copy). The memorandum treats the cost of replacing the breakers as the ascertainable loss and records that the defendants sent 48,000 notification letters in the early 1980s.

Federal Pacific, Zinsco and related findings by evidence level, 1983 to 2026 Download CSV
DateProductBodyActionEvidence levelWhat the record says
1983-03-03Federal Pacific Electric Stab-Lok residential breakersCPSCInvestigation closed, no recallCPSC statementData did not establish a serious risk of injury; CPSC testing confirmed breakers failed certain UL calibration tests; staff had insufficient data to accept or refute Reliance's safety position
2011-02-18Federal Pacific Electric Stab-Lok residential breakersCPSCNote added to 1983 releaseCPSC statementCommission closed the matter without a determination as to the safety of FPE circuit breakers
1991-01-22FPE investigation recordsU.S. Court of Appeals, D.C. CircuitFOIA disclosure ruling (Reliance Electric v. CPSC)Court recordDescribes the CPSC probe as inconclusive; about 500 pages cleared for release by the district court; affirmed in part, vacated and remanded in part
2002-08-15Federal Pacific Electric breakers sold 1965 to 1980Superior Court of New Jersey, Middlesex CountyMemorandum of decisionCourt findingFPE knowingly and purposefully distributed circuit breakers which were not tested to meet UL standards as indicated on their label (NJ Consumer Fraud Act)
2002-10-29Federal Pacific Electric breakersSuperior Court of New Jersey, Middlesex CountyOrder for partial summary judgmentCourt findingSummary judgment against FPE on the Consumer Fraud Act issue; claims on pre-June 29, 1971 sales and by subsequent home buyers dismissed
2022-06-16Square D QO Plug-On Neutral loadcentresHealth CanadaRecall (cross-border entry)Health Canada recall289,694 units sold in Canada; overheating could pose a fire hazard
2019-05Federal Pacific Stab-Lok panels and breakersAmTrust (insurer)Loss-control bulletinInsurer statement, Tier 2Recommends replacing all Federal Pacific Stab-Lok panels and breakers with UL Listed equipment
2024-03-29Stab-Lok type breakers (FPE and other brands)J. Aronstein, P.E.Engineering test reportEngineer report, Tier 2Independent tests: 42% of 718 FPE double-pole and 13% of 1,726 single-pole breakers failed to trip at 135% of rating
2017-03-20Zinsco and UBI-Zinsco breakersJ. Aronstein, P.E. (via InspectAPedia)Engineering test resultsEngineer report, Tier 232 of 111 Zinsco-type breakers (28.8%) failed the UL 489 135% trip requirement; 2 jammed
2026-10-27Zinsco, Sylvania-Zinsco, Federal PacificCPSC and Health Canada recall databasesDatabase queryAbsence of record0 recall records name Zinsco, Sylvania-Zinsco, Federal Pacific or Stab-Lok

Evidence levels: CPSC statement, court finding, court record, Health Canada recall, insurer statement (Tier 2), engineer report (Tier 2), absence of record (database query). Engineer and insurer entries are not agency findings.

Source: [21][22][23][24][25][26][27][29][1] U.S. Consumer Product Safety Commission; Superior Court of New Jersey, Law Division, Middlesex County (copy hosted by InspectAPedia); U.S. Court of Appeals for the D.C. Circuit (text via Public.Resource.Org); Health Canada; Government of Canada (Health Canada and partner agencies); J. Aronstein, consulting engineer (N.Y.S. P.E.); AmTrust North America, Florida Region; InspectAPedia (D. Friedman), reporting tests by J. Aronstein; U.S. Consumer Product Safety Commission (SaferProducts.gov)

Engineering data are the main public evidence on how Stab-Lok breakers perform. Engineer J. Aronstein's compilation reports that 42% of 718 FPE double-pole breakers and 13% of 1,726 single-pole breakers he and a colleague tested failed to trip at 135% of rated current, the UL calibration point (Aronstein, 2024). The same report estimates about 2,800 residential electrical fires a year associated with defective Stab-Lok operation, with 116 injuries, 13 deaths and $40 million in property loss; the author describes the estimate as not exact. These are Tier 2 engineering figures, not CPSC findings.

Published trip-test results for FPE Stab-Lok breakers (engineer's compilation, Tier 2) Download CSV
TesterBreaker typeTestedFailed to trip at 135% of ratingCritical failures (no trip at 200% or jammed)
CPSCsingle-pole144 (28%)1 (7%)
CPSCdouble-pole2720 (74%)5 (19%)
Wright-Malta (for CPSC)Wright-Malta for double-pole12262 (51%)12 (10%)
Independentsingle-pole1,726222 (13%)6 (0.3%)
Independentsingle-pole GFI/breaker86 (60%)4 (50%)
Independentdouble-pole718285 (42%)59 (8%)

Reproduced from Table 1 of J. Aronstein, Hazardous FPE Circuit Breakers and Panels (updated March 29, 2024; data as of October 27, 2017). The report states copies may be freely distributed. Samples are not random. Not an agency finding.

Source: [26] J. Aronstein, consulting engineer (N.Y.S. P.E.)

Engineering trip tests found high failure rates in FPE and Zinsco breakers

Share of tested breakers that failed to trip at 135% of rated current (Tier 2 engineering data, not agency findings)

Engineering trip tests found high failure rates in FPE and Zinsco breakersHorizontal bar chart of trip-test failure rates at 135% of rating reported by engineer J. Aronstein: 74% of 27 FPE double-pole breakers in CPSC tests, 51% of 122 in Wright-Malta tests for CPSC, 42% of 718 in independent tests, 28.8% of 111 Zinsco-type breakers, 28% of 14 FPE single-pole breakers in CPSC tests and 13% of 1,726 independent single-pole tests.percentCPSC tests, FPE double-pole (27 tested)74.0Wright-Malta for CPSC, FPE double-pole (1251.0Independent, FPE double-pole (718)42.0Independent, Zinsco-type (111)28.8CPSC tests, FPE single-pole (14)28.0Independent, FPE single-pole (1,726)13.0

Source: J. Aronstein, Hazardous FPE Circuit Breakers and Panels (2024), Table 1; InspectAPedia summary of Aronstein Zinsco tests (2017)

No Zinsco panel or Sylvania-Zinsco breaker appears in any CPSC recall

For Zinsco, the official record is an absence: no recall, no CPSC statement and no court ruling on product performance was found. The only quantitative evidence is a small engineering test sample.

A search of all 10,058 records in the CPSC recall database (titles, product names and descriptions) returned 0 recalls naming Zinsco or Sylvania-Zinsco. The Health Canada recalls open data file (34,290 records through October 23, 2026) also returned 0 (Health Canada). ECW found no CPSC news release on Zinsco and, among the sources it could open, no court ruling on Zinsco breaker performance.

  • What the record shows: Zinsco-type breakers have been bench tested by an engineer. Test results summarized by InspectAPedia report that 32 of 111 Zinsco-type breakers (28.8%) retrieved from in-use panels failed the UL 489 requirement to trip at 135% of rated current, and 2 (1.8%) jammed, as of March 20, 2017 (Tier 2).
  • For Zinsco-brand breakers alone, the same summary reports a 26.2% failure rate at 135%. The page also cites a count of 98 Zinsco plus 3 UBI breakers, which does not match the 111 total, so the sample size is uncertain.
  • What the record does not show: any agency or court finding that Zinsco equipment is defective, any recall remedy, or any measured fire rate for homes with Zinsco panels.

Zinsco and Sylvania-Zinsco: Panels and breakers sold under the Zinsco name and under GTE-Sylvania or Sylvania-Zinsco labels, which InspectAPedia describes as the same product design and origin. Identification is a job for a licensed electrician, who can open the panel safely.

Readers who own Zinsco or Sylvania-Zinsco equipment and see heat damage, buzzing or breakers that will not reset can report a product problem to CPSC at SaferProducts.gov and should have a licensed electrician inspect the panel. See how to hire an electrician.

Square D labels appear on 12 of the 19 recalls, five of them counterfeits

Brand counts reflect market share as much as defects: Square D and Siemens are among the largest residential breaker makers, and five recalls involved fakes sold under the Square D name.

Challenger. The only Challenger recall in the CPSC database is a November 12, 1988 free replacement program for 15 and 20 A type HAGF single-pole GFCI breakers made February 22 to April 29, 1988. CPSC said a mechanical part could detach and disable the ground-fault feature, that about 9,000 of the breakers had not been located, and that normal breaker functions were not affected (CPSC recall 88095). No CPSC recall covers Challenger panels as such. Challenger Electric Company was also named as a defendant in the New Jersey FPE case; the reviewed order grants summary judgment only against FPE and does not rule on Challenger.

Square D. Genuine Square D products account for 7 recalls and about 2.3 million units: Series 1 GFCI breakers (1988), combination service entrance devices (1999), MA/MH breakers (2002), QO and Homeline AFCI breakers (2004), F and K frame breakers (2014), PowerPact J-frame breakers (2014) and QO Plug-On Neutral load centers (2022). The 2022 recall is the only Square D recall of a stand-alone residential load center (CPSC recall 22159).

Counterfeits. Five distributors recalled 558,600 counterfeit breakers labeled Square D between 2006 and 2010. CPSC said the fakes could fail to trip when overloaded and listed visual features of genuine QO breakers (CPSC recall 08286).

Siemens, Murray and I-T-E. Four recalls cover about 2.3 million units: I-T-E load centers (1988), 2-pole GFCI breakers for spas (1998), breakers, load centers and meter combos (2010) and SolarReady meter combos (2024) (CPSC recall 10354). Eaton (2014 meter breakers, about 1,100 units) and Midwest and GE (2004 meter load centers, 2,754 units) have one recall each.

CPSC panel and breaker recalls by brand group, US, 1988 to 2024 Download CSV
Brand groupRecallsUS units coveredYears
Square D (genuine)72,323,1001988, 1999, 2002, 2004, 2014, 2014, 2022
Counterfeit labeled Square D5558,6002006, 2007, 2007, 2008, 2010
Siemens, Murray or I-T-E42,347,9101988, 1998, 2010, 2024
Challenger19,0001988
Eaton11,1002014
Midwest and GE12,7542004

Counterfeit breakers carried Square D labels but were not made by Square D; the recalling firms were distributors.

Source: [1] U.S. Consumer Product Safety Commission (SaferProducts.gov)

CPSC panel and breaker recalls by product type, US, 1988 to 2024 Download CSV
Product typeRecallsUS units coveredMain hazard group
Counterfeit breaker5558,600Overheating, fire or failure to trip
Meter-main combination419,964Shock or arcing from the enclosure
GFCI breaker3233,000GFCI or AFCI protection may not work
Circuit breaker3130,900Overheating, fire or failure to trip
Load center21,400,000Overheating, fire or failure to trip
AFCI breaker1700,000GFCI or AFCI protection may not work
Breakers, load centers and meter combos12,200,000Overheating, fire or failure to trip

Product types and hazard groups are ECW groupings of CPSC product and hazard text.

Source: [1] U.S. Consumer Product Safety Commission (SaferProducts.gov)

Assorted plug-in residential circuit breakers on a workbench
Illustrative photograph. Generated image, not a specific project.

Recall counts peaked in the 2000s and recalled units in the 2010s

Seven recalls were announced in the 2000s, but the 2010s covered the most units because of one 2.2 million unit recall. Counts this small swing on single events.

Panel and breaker recalls peaked in the 2000s

CPSC recalls of panels, load centers, meter-main combinations and circuit breakers by decade announced, US

Panel and breaker recalls peaked in the 2000sBar chart of CPSC panel and breaker recalls by decade: 3 in the 1980s, 2 in the 1990s, 7 in the 2000s, 5 in the 2010s and 2 in the 2020s through October 2026.02468recalls31980s21990s72000s52010s22020s

Source: U.S. Consumer Product Safety Commission recall database, queried 2026-10-27; ECW classification

Recalled units peaked in the 2010s

US units covered by CPSC panel and breaker recalls, by decade announced, thousands

Recalled units peaked in the 2010sBar chart of recalled units by decade: about 89,000 in the 1980s, 156,200 in the 1990s, 1,257,754 in the 2000s, 2,335,600 in the 2010s and 1,403,910 in the 2020s.01,0002,0003,000thousand units89.01980s1561990s1,2582000s2,3362010s1,4042020s

Source: U.S. Consumer Product Safety Commission recall notices; ECW sum of published unit counts

CPSC panel and breaker recalls and units covered by decade of announcement, US Download CSV
DecadeRecallsRecalls stating unitsUS units covered
1980s3289,000
1990s22156,200
2000s771,257,754
2010s552,335,600
2020s221,403,910
Total19185,242,464

Unit totals sum the approximate counts CPSC published; one 1980s recall (Siemens I-T-E load centers) states no count.

Source: [1] U.S. Consumer Product Safety Commission (SaferProducts.gov)

The 2000s total of 7 includes four counterfeit breaker recalls; without them the decade would show 3. The 2020s so far hold 2 recalls and 1,403,910 units, almost all from the 2022 Square D load center recall. With 796 days between the most recent recall (August 22, 2024) and the database query, the register shows no new panel or breaker recall in 26 months.

The CPSC database is thin before the 1990s, and recall counts reflect reporting and enforcement as well as product quality. These decade figures describe the recall record, not failure rates.

Every CPSC panel and breaker recall offered a free remedy

All 19 notices offered free replacement, repair, inspection or a refund; most route the work through electricians or the manufacturer rather than asking owners to handle equipment.

The remedies below are quoted or closely paraphrased from CPSC notices. They apply only to the specific models and date codes each notice lists.

  • Square D QO Plug-On Neutral load centers (2022): owners should contact Schneider Electric to arrange inspection by trained electricians; the inspection and any resulting repair or replacement are free of charge, and owners awaiting repair should have working smoke alarms (CPSC).
  • Siemens SolarReady meter combos (2024): Siemens arranges an on-site inspection and repair or replacement by a licensed contractor at no cost (CPSC).
  • Siemens and Murray breakers, load centers and meter combos (2010): free inspection by an electrician and free replacement (CPSC).
  • Eaton meter breakers (2014): consumers should not open the enclosure; Eaton or the installing contractor installs a free repair kit (CPSC).
  • Siemens and Murray spa GFCI breakers (1998): consumers should not attempt to remove the breaker because high voltage can cause death or serious injury; Siemens arranges replacement at no charge (CPSC).

Federal Pacific and Zinsco have no recall remedy because they have no recall. CPSC's 1983 release advised consumers with any brand of breaker to investigate why a breaker trips rather than simply resetting it, and to consult a licensed electrician when in doubt (CPSC).

Outdoor meter and main breaker enclosure on a house wall
Illustrative photograph. Generated image, not a specific project.

What this record cannot tell you

A recall register measures corrective actions, not failure rates, and it misses products that were never recalled.

  • Recall counts depend on firms reporting problems and CPSC acting; a brand with no recall is not thereby shown to be safe or unsafe.
  • Unit counts are approximate figures published by firms through CPSC and are not adjusted for units still in service.
  • The CPSC database holds few records from before about 1990; recalls from the 1970s and early 1980s may be missing.
  • Engineering test results for FPE and Zinsco come from samples submitted from the field, not random samples, and have not been replicated by an agency.
  • Local electrical codes, adopted under the NEC, govern panel replacement; see the site's code section.

The record in numbers

  1. CPSC announced 19 recalls of US panels, load centers, meter-main combinations and circuit breakers between April 13, 1988 and August 22, 2024.[1]
  2. Those recalls covered about 5.2 million US units where a count was published; 18 of the 19 notices state a unit count.[1]
  3. The largest single recall, announced September 23, 2010, covered about 2.2 million Siemens and Murray circuit breakers, load centers and meter combos with a spring clip that can break.[15]
  4. Square D QO Plug-On Neutral load centers made February 2020 to January 2022 were recalled June 16, 2022: about 1.4 million in the US and 289,694 in Canada, per Health Canada.[19][24]
  5. About 700,000 Square D QO and Homeline AFCI breakers were recalled November 3, 2004 because an electronic component failure could stop them detecting arcs.[8]
  6. Five recalls from 2006 to 2010 covered 558,600 counterfeit breakers labeled Square D, 10.7% of all recalled units.[10][11][12][13][14]
  7. No CPSC recall record from 1973 to October 22, 2026 names Zinsco, Sylvania-Zinsco, Federal Pacific or Stab-Lok.[1]
  8. On March 3, 1983, CPSC closed its 2-year investigation of Federal Pacific Electric Stab-Lok breakers, saying its data did not establish a serious risk of injury, while confirming the breakers failed certain UL calibration tests.[21]
  9. On February 18, 2011, CPSC added a note that it had closed the FPE matter without making a determination as to the safety of FPE circuit breakers.[21]
  10. On August 15, 2002, a New Jersey Superior Court judge found Federal Pacific Electric knowingly and purposefully distributed breakers not tested to meet UL standards as labeled, a Consumer Fraud Act violation.[22]
  11. The 1988 Challenger recall covered type HAGF GFCI circuit breakers, about 9,000 of which had not been located; CPSC said normal breaker functions were not affected.[3]
  12. All 19 CPSC panel and breaker recall notices offered a free remedy; 2 of them, both commercial molded case breaker recalls, added a labor allowance of up to $300.[16][18]
  13. None of the 19 recall notices reports an injury; three report a fire or possible fire (2004 AFCI, 2004 meter load center, 2024 SolarReady).[8][9][20]
  14. In tests compiled by engineer J. Aronstein, 42% of 718 FPE double-pole Stab-Lok breakers failed to trip at 135% of rated current (Tier 2 engineering data, not an agency finding).[26]

Rates we calculated

CPSC panel and breaker recalls by decade

Formulacount of register entries by decade of announcement

Inputs: fact sheet rows 3 to 21 (recall dates); derived d1_1980s to d1_2020s (fact sheet rows)

Result: 1980s 3; 1990s 2; 2000s 7; 2010s 5; 2020s 2; total 19

Recalls cluster in the 2000s, driven by four counterfeit breaker recalls; there has been no panel or breaker recall since August 2024.

Limitations: Scope decisions are ECW's; the database is sparse before the 1990s.

Total units recalled where CPSC states a count

Formulasum of US unit counts in 18 recall notices

Inputs: fact sheet unit rows for each recall; derived d2_total_units (fact sheet rows)

Result: 5,242,464 units (about 5.2 million)

Most recalled units are recent and residential: 5,111,564 units were in residential-segment recalls.

Limitations: Counts are approximate; 88095 counts breakers not yet located; Canadian units excluded.

Evidence-level labels

Formulacount of dated entries in tables t1 and t2 by evidence level

Inputs: tables t1, t2; derived d3 rows (fact sheet rows)

Result: 29 entries: 19 CPSC recalls, 2 CPSC statement entries, 2 court finding entries, 1 court record, 1 Health Canada recall, 1 insurer statement, 2 engineer reports, 1 absence of record

Federal Pacific's record rests on a CPSC statement and a state consumer fraud ruling, not a recall; Zinsco's rests on engineering tests only.

Limitations: One source can produce two entries (the 1983 release and its 2011 note; the 2002 memorandum and order).

Share of recalls with a free remedy

Formularecalls offering free repair, replacement, inspection or refund / 19 x 100

Inputs: remedy text for all 19 recalls; derived d4_free_n, d4_free_share (fact sheet rows)

Result: 19 of 19 (100%); 2 added a labor allowance

Every panel and breaker recall shifted the cost of correction to the firm.

Limitations: Notices do not report how many owners received the remedy.

Concentration of recalled units

Formula(2,200,000 + 1,400,000) / 5,242,464 x 100

Inputs: fact sheet rows for recalls 10354 and 22159; derived d2_total_units (fact sheet rows)

Result: 68.7%

Two recalls of mainstream residential equipment outweigh the other 16 recalls with counts combined.

Limitations: Approximate counts.

Counterfeit share

Formulacounterfeit recalls / 19; counterfeit units / total units

Inputs: fact sheet rows for recalls 07036, 08054, 08151, 08286, 10749 (fact sheet rows)

Result: 5 recalls (26.3%); 558,600 units (10.7%)

About a quarter of panel and breaker recalls involved fake breakers sold through distribution, not manufacturer defects.

Limitations: Counterfeit recalls cluster in 2006 to 2010; later counterfeit seizures handled outside CPSC recalls are not counted.

Get the calculations (CSV)

What people search for

Are Zinsco panels dangerous?

No US agency or court has made a finding on Zinsco panels: the CPSC and Health Canada recall databases hold 0 Zinsco records as of October 2026. The only test data ECW found are engineer J. Aronstein's: 32 of 111 Zinsco-type breakers (28.8%) failed to trip at 135% of rated current as of March 2017 (Tier 2). A licensed electrician can assess a specific panel.

Was Federal Pacific ever recalled?

No. CPSC closed its investigation of Federal Pacific Electric Stab-Lok breakers on March 3, 1983 without a recall, and in 2011 added that it had made no determination about their safety (CPSC). A New Jersey court found consumer fraud over UL testing and labels in 2002 (court papers).

Are Stab-Lok breakers safe?

No agency has ruled either way. CPSC testing confirmed Stab-Lok breakers failed certain UL calibration tests, but CPSC said in 1983 it could not link those failures to a hazard (CPSC). Engineer test data report that 42% of 718 FPE double-pole breakers failed to trip at 135% of rating (Tier 2).

Which Challenger panels were recalled?

None as panels. CPSC's only Challenger recall, announced November 12, 1988, covered type HAGF-15 and HAGF-20 GFCI circuit breakers made February 22 to April 29, 1988; about 9,000 had not been located (CPSC).

Was there a Square D panel recall?

Yes. On June 16, 2022, Schneider Electric recalled about 1.4 million Square D QO Plug-On Neutral load centers made February 2020 to January 2022 because they can overheat, with free inspection and repair or replacement (CPSC). Square D brand products appear in 7 genuine recalls since 1988.

Does insurance cover Federal Pacific panels?

ECW found no federal or state rule on coverage. One insurer, AmTrust, published a May 2019 loss-control bulletin that recommends replacing all Federal Pacific Stab-Lok panels and breakers (AmTrust). Coverage decisions are set by each insurer; ask the carrier directly.

In short

  • The CPSC recall database holds 19 recalls of panels, load centers, meter-main combinations and circuit breakers (including AFCI and GFCI breakers) announced from 1988 to 2024, queried October 27, 2026.
  • Those 19 recalls covered about 5.2 million units in the United States where CPSC published a count (18 of 19 recalls).
  • Two recalls account for 68.7% of recalled units: Siemens and Murray breakers, load centers and meter combos (about 2.2 million, 2010) and Square D QO Plug-On Neutral load centers (about 1.4 million, 2022).
  • No CPSC or Health Canada recall names Zinsco, Sylvania-Zinsco, Federal Pacific or Stab-Lok products.
  • For Federal Pacific Stab-Lok, the official record is a 1983 CPSC statement closing a 2-year investigation without a safety determination and a 2002 New Jersey court finding of consumer fraud over UL testing and labeling.
  • Every one of the 19 CPSC recall notices offered a free remedy: replacement, repair, inspection or refund (100%).
  • Five of the 19 recalls (26.3%) were counterfeit breakers labeled Square D, covering 558,600 units from 2006 to 2010.
  • The most recent US panel or breaker recall is the Siemens SolarReady meter combo recall of August 22, 2024 (about 3,910 units), 796 days before the database query.

Common questions

How many electrical panels and breakers has CPSC recalled?

The CPSC recall database lists 19 recalls of panels, load centers, meter-main combinations and circuit breakers from 1988 to 2024, covering about 5.2 million US units where a count is published.

What was the largest electrical panel or breaker recall?

Siemens and Murray circuit breakers, load centers and meter combos, recalled September 23, 2010: about 2.2 million units with a spring clip that can break during normal use (CPSC).

When was the most recent panel or breaker recall?

August 22, 2024, when Siemens recalled about 3,910 SolarReady meter combos for an interior connection that can overheat. No panel or breaker recall was announced in 2025 or 2026 through the October 27, 2026 query (CPSC).

Have AFCI breakers been recalled?

Yes. On November 3, 2004, about 700,000 Square D QO and Homeline AFCI breakers were recalled because an electronic component failure could stop them detecting an arc; they still worked as regular breakers (CPSC).

Have GFCI breakers been recalled?

Three GFCI breaker recalls appear: Square D Series 1 two-pole (1988, approximately 80,000), Challenger HAGF (1988, about 9,000 not located) and Siemens and Murray 2-pole spa breakers (1998, about 144,000) (CPSC).

What are counterfeit Square D breakers?

Breakers labeled Square D but not made by Square D. Five distributors recalled 558,600 of them from 2006 to 2010 because they could fail to trip when overloaded (CPSC).

What did the New Jersey court decide about Federal Pacific?

On August 15, 2002, the Superior Court of New Jersey found FPE knowingly and purposefully distributed breakers not tested to meet UL standards as labeled, violating the Consumer Fraud Act; the October 29, 2002 order granted partial summary judgment against FPE.

Is Federal Pacific Equipment the same as Federal Pacific Electric?

No. The New Jersey class notice states that Federal Pacific Equipment Inc. is a different company from Federal Pacific Electric Company and its breakers were not included in the claim (class notice text, Tier 3).

Did CPSC ever test Federal Pacific breakers?

Yes. CPSC's 1983 release says Commission testing confirmed FPE breakers fail certain UL calibration test requirements, focused mainly on 2 pole residential breakers made before 1979. An engineer's account puts the CPSC failure rates at 85% of double-pole and 39% of single-pole samples.

How can I tell if my panel is part of a recall?

Each CPSC notice lists brands, catalog numbers and date codes, often inside the panel door. Because panels carry live voltage, CPSC notices for load centers and meter combos route identification and repair through electricians or the manufacturer.

Get the data

Every table in this report is available as a CSV under CC BY 4.0. The fact sheet lists each value with its source URL and access date.

Cite this report

The figures to cite first

  1. 19 CPSC recalls of panels, load centers, meter-main combinations and circuit breakers, 1988 to 2024, covering about 5.2 million US units.[1]
  2. 0 CPSC recalls name Zinsco or Federal Pacific; the Federal Pacific record is a 1983 CPSC statement and a 2002 New Jersey consumer fraud ruling.[1][21][22]
  3. The latest US panel or breaker recall was announced August 22, 2024 (Siemens SolarReady meter combos, about 3,910 units).[20]

Quotable figures

  • No CPSC recall from 1973 to October 2026 names Zinsco, Sylvania-Zinsco, Federal Pacific or Stab-Lok products.[1]
  • CPSC has recalled 19 US panel, load center, meter-main and circuit breaker products since 1988, covering about 5.2 million units.[1]
  • Two recalls, Siemens and Murray in 2010 and Square D QO Plug-On Neutral load centers in 2022, account for 68.7% of recalled panel and breaker units.[15][19]
  • CPSC closed its Federal Pacific Stab-Lok investigation on March 3, 1983 and later said it had made no determination about the breakers' safety.[21]
  • A New Jersey court found in 2002 that Federal Pacific Electric knowingly and purposefully distributed breakers not tested to meet UL standards as labeled.[22]
  • Five of 19 panel and breaker recalls (26.3%) were counterfeit breakers labeled Square D, covering 558,600 units.[1]
  • All 19 CPSC panel and breaker recalls offered a free remedy.[1]

Summary for editors

No U.S. Consumer Product Safety Commission recall record names Zinsco or Federal Pacific panels, according to an Electrical Contractors and Wiring analysis of the full CPSC recall database downloaded October 27, 2026. The database lists 19 recalls of panels, load centers, meter-main combinations and circuit breakers from 1988 to 2024, covering about 5.2 million US units. Two recalls, Siemens and Murray equipment in 2010 and Square D QO Plug-On Neutral load centers in 2022, hold 68.7% of those units. Five recalls involved counterfeit breakers labeled Square D. All 19 offered a free remedy. For Federal Pacific Stab-Lok breakers, the official record is a 1983 CPSC statement closing a 2-year investigation without a safety determination and a 2002 New Jersey court finding that the company distributed breakers not tested to UL standards as labeled. For Zinsco, ECW found no recall, agency statement or court finding; engineering tests on 111 breakers are the only data. No panel or breaker recall has been announced since August 2024.

Headlines the data supports

  • No Zinsco or Federal Pacific panel has ever been recalled, CPSC records show
  • 19 panel and breaker recalls since 1988 covered 5.2 million units
  • Two recalls hold 68.7% of all recalled panel and breaker units
  • What CPSC and a New Jersey court actually said about Federal Pacific Stab-Lok
  • One in four panel and breaker recalls involved counterfeit Square D breakers

Citation

Electrical Contractors and Wiring. (2026). Zinsco Panel, Federal Pacific and Circuit Breaker Recalls: What Agencies and Courts Found. Retrieved from https://electricalcontractorsandwiring.com/data/electrical-panel-recalls/

Reuse

Data and tables are licensed CC BY 4.0. Attribution: “Source: Electrical Contractors and Wiring, Zinsco Panel, Federal Pacific and Circuit Breaker Recalls: What Agencies and Courts Found” with a link to this page.

How we built this report

Selection: ECW downloaded the full CPSC recall database through the keyless SaferProducts.gov Recalls Retrieval Web Service on October 27, 2026 (10,058 records dated 1973 to October 22, 2026). Every record whose title, product name, product type or description mentions breakers, panels, load centers, panelboards, AFCIs, GFCIs, interrupters, meter combinations or major panel brands was reviewed by hand. Nineteen recalls of panels, load centers, meter-main combinations and circuit breakers (including AFCI and GFCI breakers) were included. GFCI receptacles, plug-in and cord GFCIs, surge devices, safety switches, transfer switches and meter sockets without a breaker were excluded. Each included recall's CPSC notice page was saved.

Unit counts, hazards, incidents and remedies are copied from each CPSC record. Where the API record lacked a count (Square D combination service entrance devices, 1999), the count comes from the CPSC notice page. The database lists the Siemens I-T-E notice under 1998, but the notice text says it was originally issued November 1, 1988 and its recall number begins with 88; ECW uses 1988. The Challenger count is CPSC's figure for breakers not yet located.

Evidence levels: CPSC recall; CPSC statement; court finding (a ruling on the merits); court record (a ruling on another question); Health Canada recall (cross-border, labeled); engineer report and insurer statement (Tier 2, not agency findings); absence of record (a database query returning no match). Court papers for the New Jersey case were read from a scanned copy of the August 15, 2002 memorandum and October 29, 2002 order hosted by InspectAPedia; the original court file was not available online.

Conflicts: CPSC reports 289,000 Square D Plug-On Neutral load centers sold in Canada and Health Canada reports 289,694; the Health Canada figure is used for Canada. The AmTrust bulletin attributes the 2002 ruling to a New York statute; the court papers show the New Jersey Consumer Fraud Act. The InspectAPedia Zinsco summary gives both 111 and 98 plus 3 as sample sizes; the 111 total is reported with that caveat.

Derived metrics (counts by decade, units, shares, evidence-level counts, days since the last recall) are computed in scripts/build_data.py and listed with formulas and input rows in derived_metrics.csv.

Limitations: recalls measure corrective actions, not failure or fire rates; the database is sparse before the 1990s; unit counts are approximate; engineering samples are not random. Last updated October 27, 2026.

This report presents published data with its limitations. It is not legal, financial or investment advice.